Fixed gas detection: designing, installing and maintaining a system that works
A fixed gas detection system protects life and property only when it is designed around the real hazards, placed where gas will travel and maintained for the life of its sensors. Its early warning buys time to evacuate, start ventilation or suppression, or shut down a process. Because gas detection is driven more by industry practice than by code, each site has to understand its own hazards and the local and federal rules that apply.
Drawing on a three-part webinar series, this article covers gas hazards, detection technologies, planning and placement, equipment selection and maintenance.
Gas hazards and how they are measured
A gas expands indefinitely, moves at high speed and mixes rapidly into any atmosphere it is released into. Gas detection deals with three main hazards:
Combustible gas limits
The lower explosive limit (LEL) is the minimum concentration of gas in air that can ignite. Below it, the mixture is too lean to burn. The upper explosive limit (UEL) is the maximum. Above it, the mixture is too rich. The range between them is the flammable or explosive range. You may also see LFL and UFL, for lower and upper flammable limits, which mean the same things.
Combustible concentrations are expressed as a percentage by volume or as %LEL. For methane, the main component of natural gas, 100% LEL equals 5% by volume in air. Other common combustibles include propane, hydrogen, methanol, ethane and ethanol.
Toxic exposure limits
For toxic gases, both concentration and length of exposure matter. The industry uses several terms:
| Term | Meaning |
|---|---|
| PEL (permissible exposure limit) | The exposure limit for a specific substance, usually a time-weighted average (TWA) over an eight-hour workday |
| STEL (short-term exposure limit) | A limit that is safe for a shorter exposure, generally 15 minutes |
| TLV (threshold limit value) | The level a worker can be exposed to day after day for a working lifetime without adverse effects |
| IDLH (immediately dangerous to life or health) | The most dangerous level for a toxic gas |
These limits are usually expressed in parts per million (ppm) or parts per billion (ppb). Picture a room filled with 1 million balls, one of them red. That red ball is 1 ppm. Among 1 billion balls, it would be 1 ppb.
Common toxic gases in chemical and petrochemical plants include ammonia, carbon monoxide, chlorine, hydrogen sulfide, nitric oxide, nitrogen dioxide and sulfur dioxide. Others include hydrogen chloride, hydrogen cyanide and phosgene.
Oxygen levels
Normal air holds 20.9% oxygen by volume, and oxygen sensors typically read 0 to 25% by volume. A typical first alarm triggers when oxygen drops below 19%, around where symptoms such as dizziness, nausea and lightheadedness begin. A second alarm at 23% warns of enrichment, which makes ordinary materials easier to ignite. At 25%, it takes little energy for clothing to catch fire.
Where gas detection is needed
- Food and beverage processing where dangerous gases may be used or produced
- Power generation from fossil fuel plants to wind power and biogas
- Water purification and wastewater treatment which produce toxic and combustible hazards
- Refrigeration from food manufacturing to cryogenics and LNG shipping, where ammonia must not build up to toxic or explosive levels
- Laboratories and hospitals which use flammable and toxic substances and may run their own utilities and backup power
- Parking garages and tunnels where exhaust can build up carbon monoxide and methane and gas detection can control ventilation
Detection may also be needed in aviation, confined spaces, perimeter monitoring, painting operations and during planned equipment modifications.
How gas detectors work
Five technologies cover most fixed gas detection. Each has strengths and limits, so a thorough site analysis should drive the choice.
Comparing the technologies
| Technology | Strengths | Limitations |
|---|---|---|
| Catalytic bead | Low cost, accurate and linear, broadband, proven track record | Needs oxygen, can be poisoned, high power use, cannot identify the gas, readings may not reflect true concentration |
| Infrared | No oxygen needed, immune to typical poisons, low power, stable, available for 100% by volume methane, five-year mean time between failures | Cannot detect hydrogen, acetylene or carbon disulfide; costs more; more affected by temperature and pressure; linear only to its calibration gas |
| PID | Sensitive to ppm levels, accurate and linear, no oxygen needed, lamp self-cleans with ozone | Broadband, so it cannot identify the specific gas; drawn-in dirt and humidity mean more maintenance |
| Electrochemical | Low cost, ppm sensitivity, accurate and linear, typically fails safe, compact, low power, one to three year life | Cross-sensitivity, such as between CO and hydrogen; contamination by alcohols or citrus oils; some cells sensitive to humidity and temperature |
| Paper tape | Highly sensitive, specific to the target gas, accurate, wide range of tapes | Complex and expensive, tapes have a shelf life, sensitive to temperature, pressure and humidity |
Understanding the application
Every design starts with the risks. Before choosing equipment, answer four questions:
Which gases?
Toxic, combustible or oxygen-depleting, with their exposure limits and densities.
Where could they leak?
Seals, flanges, fittings, valves, storage, loading areas and decomposing material.
Who and what is at risk?
Workers, equipment, confined spaces and neighboring communities.
What should the system do?
Warn only, or also control ventilation, shut down processes and trigger emergency response.
With those answers in hand, identify the regulations that govern the application, whether local or federal.
Release and receptor points
Beyond the obvious leak sources, release points can include welds, expansion joints, gaskets, engine combustion and runoff areas. On the receptor side, consider wind direction and ventilation systems, which carry gas toward people and equipment, along with runoff areas and the facilities surrounding the site.
Design goals
Once you know what the system must do, design goals should also account for:
- The amount of confinement, over-pressurization or accumulation in an area
- How far an ignited combustible release could travel
- Congestion or obstacles between the gas and the sensors
- Fuel quantities and mixes
- The margin of safety between leak sources and receptors
- Plant safety processes and insurance requirements
Gas characteristics
For combustible gases, know where you are relative to the lower and upper explosive limits. Every gas has its own vapor density, and density can vary with temperature, which affects cryogenic and flammable liquids. Gases under pressure can also condense in an area, which matters for both ventilation and detector placement.
Some gases form from other materials, as dry ice turns into CO2. Some hydrolyze, as fluorine can turn into an acid depending on humidity. Some target gases must pass through a pyrolyzer, a heater that changes their composition so they can be monitored.
For flammability, the flash point is the lowest temperature at which a liquid forms an ignitable mixture near its surface. The lower the flash point, the more easily the material ignites. Also consider evaporation rate, dispersion, fuel and oxygen mixes, ignition sources and any oxygen-enriched environments.
Profiling the plant and placing detectors indoors
Sensors should be placed as close as possible to potential leak sources. Profiling the plant means identifying its physical features, the direction of ventilation airflow and wind, and the escape routes. Protect entrances so people cannot walk into a hazardous area, and mark the escape routes clearly.
Release and receptor points
Beyond the obvious leak sources, release points can include welds, expansion joints, gaskets, engine combustion and runoff areas. On the receptor side, consider wind direction and ventilation systems, which carry gas toward people and equipment, along with runoff areas and the facilities surrounding the site.
Practical constraints
Sensors do not last forever and must be maintained, so accessibility belongs in the design. Also plan for wiring and installation, temperature and humidity, and any sources of electromagnetic or radio frequency interference. Alarm levels follow local codes, and toxic exposure limits come from NIOSH, ACGIH and OSHA.
Oxygen matters to the sensors themselves. Most electrochemical sensors need a minimal level of oxygen, roughly 10%, to function. Catalytic bead sensors require oxygen to operate at all times. Watch for anything that could poison or inhibit a sensor.
Placement guidelines
- Keep detectors within their rated temperature limits. Some applications call for sample draw or duct mount configurations.
- Avoid water, moisture, dust and dirt where possible, or plan for more maintenance. Accessories such as a deluge cover can protect the detector.
- Mount detectors about 12 inches from pumps, seals, tanks and valves when monitoring specific equipment.
- If a detector must sit farther away, consider lower alarm levels for earlier notification.
- Mount securely and avoid vibration. Use weather protection and shields as needed.
- Point sensor faces downward or as the product instructions specify. Infrared detectors are a different case.
- When in doubt about airflow, run a smoke trace to see where the ventilation actually goes.
How many detectors?
Very few published guidelines or standards define the area or volume a gas detector should cover. Smoke detectors offer a useful comparison. UL gives them a 15-foot radius, or about 900 square feet of ceiling per detector. That spacing is a good guideline but can get very costly, so it pays to understand the application.
The right number depends on gas dispersion, air movement, leak sources and their locations, ignition sources in the airflow path, and walls or barriers that could stop gas reaching a sensor.
Budget is part of the picture too.
EXAMPLE: A MIXED INDOOR SPACE
On a single liquid tank, a point detector sits at the top where the fill line is. If the tank ruptures, liquid falls into the dike wall. More detectors sit down inside it, because vapor from the spill will hang about 12 to 18 inches above grade and drift into the sensing path.
Open path detection can replace the point detectors at the base. It gives complete 360-degree coverage regardless of wind direction. With seven, eight or 10 tanks, a good approach is point detection between tanks where leaks could occur, plus 360-degree open path coverage around the whole area. NFPA 52, ISA publications and professional safety engineering firms are useful references for designing combustible gas systems.
Placing detectors outdoors
Outdoor design follows the same thinking as indoor design, with one big difference: prevailing winds replace controlled ventilation. Identify the winds that could carry vapor away from a sensor and the angle at which they arrive. Smoke traces done seasonally are one of the best ways to confirm this, and Lesman can share information on running these tests.
Structures and terrain both affect how gas migrates. Consider the size of the area, whether toxics are present, where personnel work, and where vapors could become trapped: up in columns, in low-lying areas or in confined spaces. Identify ignition sources in relation to each potential leak.
Vapor density decides height
Every gas has its own vapor density, and it drives placement indoors and out. Lighter gases rise to the ceiling. Hydrogen, for example, climbs up and finds small pockets and holes, so air currents in those spaces need attention.
Heavier gases fall to the ground. Mount detectors for them about 18 inches above grade. Some applications involve liquid spills that turn into vapor, and that height keeps the detector from being submerged.
A tighter grid of detectors outdoors helps offset dilution, which is another reason to keep sensors as close as possible to the potential leak. Account for wind shifts as well.
General considerations
- For toxic gases, identify the leak source and exit points first. Placing detectors between leak sources and where people work improves worker safety.
- Allow access for maintenance, calibration and replacement.
- Keep detectors within their temperature ranges. A sunshade or deluge cover against radiant heat helps operation and longevity.
- Keep detectors away from moisture and chemicals that are not the true source.
- Avoid vibration and mechanical shock.
- Follow recommended wiring and tagging practices. Tracking down an untagged sensor across a facility is difficult.
- Always use shielded cable to eliminate radio frequency interference, and follow proper grounding practices in NFPA 70 and local electrical codes.
- Always observe the detector's mounting orientation.
EXAMPLE: TANK FARMS
On a single liquid tank, a point detector sits at the top where the fill line is. If the tank ruptures, liquid falls into the dike wall. More detectors sit down inside it, because vapor from the spill will hang about 12 to 18 inches above grade and drift into the sensing path.
Open path detection can replace the point detectors at the base. It gives complete 360-degree coverage regardless of wind direction. With seven, eight or 10 tanks, a good approach is point detection between tanks where leaks could occur, plus 360-degree open path coverage around the whole area. NFPA 52, ISA publications and professional safety engineering firms are useful references for designing combustible gas systems.
EXAMPLE: RAIL LOADING
A rail filling station is essentially a tank yard on wheels. Put a point detector at the filling area, and instead of 360-degree coverage, run open path detectors along both sides of the track. Consider adjacent housing and facilities that vapor from the site could reach.
ISA recommended practices, ACGIH and NIOSH exposure limits, NFPA guidelines and OSHA confined space rules are all worth consulting.
Controllers versus PLCs
Gas detection controllers and programmable logic controllers are similar in theory and share similar signal inputs and outputs, but they were built for different jobs. Controllers were designed with life safety in mind. PLCs were designed for plant control operations, and many people use them to build life safety systems.
| Gas detection controller | PLC | |
|---|---|---|
| Designed for | Life safety | Plant process control |
| Programming | Simple; no certified programmer needed | Requires a trained, certified programmer |
| Alarm and fault display | Built in | Needs a separate computer or HMI |
| Software | Built in | HMI packages often require licensed software |
| Upfront hardware cost | Somewhat higher | Lower |
| Overall cost of ownership | Lower once programming and labor are counted | Higher with software and skilled labor |
The controller's higher upfront price is often offset by avoiding the PLC's software licenses, extra interface hardware and experienced programming labor.
Selecting a detector
Detectors are designed around specific applications, so selection starts with the application's requirements:
- Certifications. Each application may require different ones.
- Environment. Indoor or outdoor, corrosive exposure for the housing, temperature and humidity.
- Gas type and range.
- Output signals. Milliamp, two-wire, three-wire or four-wire connections, HART, Foundation Fieldbus, Modbus, and whether relays are needed.
- Accessibility and interface. Whether the unit is easy to reach and magnet control is enough, or whether a Bluetooth app interface offers more flexibility.
Inspections and bump testing
Regular visual inspections protect the lifetime of the equipment. A quarterly routine is typical, though cleaner sites need fewer inspections and dirtier sites more. Log the date and time of every inspection along with any relevant comments.
A visual inspection should cover:
- Junction boxes, cabling and wiring. Look for bare exposed conductors or a compromised cable shield, which can introduce transients onto power and signal lines.
- Accessories. Look for breaks, tears, cracks or excessive wear, and note any that need replacing.
- The gas path. Most important of all, confirm each sensor has a clear, unobstructed path for gas to reach it.
A bump test challenges the sensor with gas to confirm it responds. It is not a calibration. Before applying gas, inhibit the outputs so the test does not send an alarm to the control room or trigger a shutdown. Keep the same accurate log of date, time and any irregularities.
Calibration
Optical devices, such as point and open path infrared gas detectors and ultrasonic gas leak detectors, generally do not need routine calibration once installed. The exception is changing the target gas on an infrared detector, which requires recalibrating with the new gas. Catalytic bead sensors, electrochemical cells and photoionization detector (PID) sensors are consumables and need a routine calibration schedule, logged like inspections.
General rules:
- Use the proper calibration accessory. A bump test kit does not seal well enough for calibration, which needs a steady, accurate concentration of gas.
- Never assume the background is clean when zeroing. Use zero air, or confirm the area with a calibrated reference such as a portable four-gas detector (CO, oxygen, H2S and LEL) held near the sensor.
- Span with the actual target gas. PID detectors can be the exception. They may be calibrated with isobutylene and then given a correction factor for the target gas. Isobutylene is stable, has a long shelf life, and is readily available and affordable.
- Use the right concentration. Most detectors use 50% of full scale, such as 50% LEL of the target gas, usually methane. Some instruments accept 30 to 70% LEL, and a few specific models allow 100% of full scale.
- Use the right flow. Electrochemical, catalytic bead and infrared sensors each call for specific regulators. A PID detector with an internal pump uses a demand flow regulator, drawing gas as it needs it.
- Always consult the product manual.
Cleaning and sensor replacement
Cleaning keeps the gas path clear so gas can reach the sensing element. Alcohol and other carbon-based chemicals can put electrochemical and catalytic bead sensors into alarm, so inhibit the outputs before cleaning with them. On transmitters, keep the display window clean so status and gas levels stay readable.
Catalytic bead sensors, electrochemical cells and PID sensing elements have a specified lifetime, and must be replaced when it expires. Electrochemical cells also have a shelf life and should be used before the expiration date on the container. Always turn power off before changing a sensor.
How a sensor comes out depends on the design:
- Accessible cell. On some transmitters, you remove the weather protection and sensor retainer to pull the sensor body. You can replace the whole body, or open its cap and replace just the sensing cell.
- Sealed cartridge. On others, the sensing element is not accessible, and you replace the complete sensor cartridge.
- Remote sensors. Remote configurations mount the sensor high or low while the transmitter stays at an accessible 5 to 6 feet. The sensor still comes out at its own location.
- App-guided replacement. Bluetooth-enabled transmitters can walk you through removing the old sensor, fitting the new one and calibrating.
- PID sensors. Use the transmitter's change sensor function, which removes power from the intrinsically safe barrier, before removing the sensor. When fitting the new one, line up the inlet port, outlet port and connector pins exactly. A pinched pin means the unit will not function properly.
After a replacement, expect a warm-up period. The transmitter may show a fault or warm-up message until the new sensor is calibrated.
Optical gas and flame detectors
For optical devices, clean windows are the main maintenance item. Never clean them with alcohol or hydrocarbon-based solvents, because hydrocarbons are what the gas detectors are looking for.
Point infrared detectors
A point infrared hydrocarbon detector needs gas to diffuse to it, so inspect it periodically. Remove the weather protection and any dust barrier, then clean the mirror and window surfaces with a cotton bud or soft cloth and a very mild detergent. Replace the barrier and weather protection, cycle power to clear any faults, then inhibit the unit and bump test it.
Open path infrared detectors
An open path infrared detector uses a transmitter and receiver that can be hundreds of feet apart. It detects gas that drifts between them if the cloud is concentrated enough. Cleaning interrupts the optical path and changes the signal output, so put the unit into its display or maintenance mode with its handheld interface first. Clean the windows with soapy water and a soft cloth.
Re-zero the detector after any cleaning, maintenance or alignment change. Dirty windows change the source intensity reaching the receiver, and re-zeroing tells the instrument what correct energy from the source lamp looks like.
Flame detectors
Flame detectors are line-of-sight devices, so an obscured window compromises their ability to see a fire. Some, such as many triple IR designs, have no grill across the face, so the window is easy to reach. Others have a grill protecting the window. Loosen the housing screw and swing the grill open like a gate, then clean both the window and the back of the grill. On some detectors the grill is part of the self-check, and a dirty window or grill can cause a fault telling you to clean the optics.
Perform end-to-end testing at least annually, adjusted for the application and environment. Prove the release solenoid can be activated, but inhibit the output that actually releases suppression.
A test lamp verifies the detector and its unobstructed view of the threat area. It is a source of radiant energy, not a one-square-foot fire.
- Disable outputs that would cause evacuation, suppression release or other executive actions.
- Stand 10 to 25 feet from the detector, as close to on-axis as possible. The farther off-axis, the closer you need to be. Inside 10 feet, the detector may see too much visible energy and reject it as a false alarm.
- Press and hold the lamp's button and watch for the red alarm LED near the top of the window to flash.
- If nothing happens within 30 seconds, check that the lamp is fully charged and the distance and technique are correct. If it still does not respond, contact the manufacturer for service or return the detector for evaluation.
Transmitter upkeep, troubleshooting and safety
Gas detection transmitters display warning, fault and informational codes. Some are cryptic, but every code should be listed in the instruction manual, so start there before taking remedial action.
A bump test shows whether a transmitter needs re-zeroing and recalibrating. A reading within plus or minus 10% of full scale is acceptable, because the gas cylinder has its own tolerance. On a 0 to 100 range tested with 50, a reading between 40 and 60 passes.
Catalytic bead sensors burn combustible gas. Poisons carried in those compounds cannot be burned off and block active sites on the pellistor, and with enough sites blocked the sensor stops detecting gas. That is why combustible detectors need regular challenges. Non-dispersive infrared sensors do not interact with or consume anything, so they are typically immune to those poisons and last longer. Electrochemical cells consume a little electrolyte as gas diffuses through their membrane.
| Item | Interval or expectation |
|---|---|
| Transmitter visual inspection | Every 3 months |
| Functional gas (bump) test | Every 6 months |
| Electrochemical cells (toxic, oxygen) | Usually more than 24 months |
| Catalytic bead (pellistor) sensors | About 3 years, depending on gas exposure |
| Combustible detector gas challenge | Every 3 to 6 months |
Working safely
- Carry a portable gas detector into the area to confirm it is free of hazardous gas before maintenance.
- Power down the instrument before replacing a sensor. On a PID detector, the change sensor function removes power from the intrinsically safe barrier instead.
- Handle sensors carefully and avoid contact with corrosive elements.
- Do not throw used sensors away. Many, especially electrochemical cells, are hazardous waste. Follow the disposal instructions in each manual.
Getting help with calibration and testing
The schedules above take time, staff and experience that many plants are short on. Kele Industrial gas detection and monitoring systems services sends trained field technicians to your site on a regular schedule to handle that work:
- Routine sensor calibrations. Full calibration of electrochemical cells and catalytic bead sensors, zero calibration and annual bump tests on infrared sensors, and response checks on open path sensors and paper tape toxic gas detector cartridges.
- System functional tests. After reviewing your cause and effect matrix, a technician confirms that sensor outputs do what they should: sound alarms, turn on lamps, send signals to your PLC or notify the local fire department.
Technicians follow manufacturer specifications and document every visit, so you have calibration records on file if questions ever come up. A well-maintained system also builds worker trust, and people who trust the system are more likely to respond when an alarm sounds.
To get started, schedule a free field service walk-through or call 800-953-7626.
Watch the full webinars
Watch the complete sessions from the three-part series, hosted by Lesman Instrument Co. and presented by Honeywell Analytics specialists:
- Fixed Gas Detection 101: Intro to Fixed Gas Detection Systems, presented by Charles Simic
- Fixed Gas Detection 201: Selection and Installation Tips, presented by Mike Holmes
- Fixed Gas Detection 301: Maintenance and Troubleshooting, presented by Charles Simic