WAGO 750-890/040-000 Controller Modbus TCP, 4th Generation XTR

Price $1,891.00

$750+ Online Orders Ship Free via UPS Ground.

Call for Availability
SKU
750-890/040-000

750-890/040-000 Controller Modbus TCP; 4th generation; 2 x ETHERNET, SD Card Slot; Extreme

  • Communications Modbus (TCP, UDP)
  • ETHERNET protocolsHTTP(S)
    • BootP
    • DHCP
    • DNS
    • SNTP
    • FTP(S)
    • SNMP
  • Visualization Web-Visu
  • CPU 32 bits
  • Programming languages per IEC 61131-3
    • Instruction List (IL)
    • Ladder Diagram (LD)
    • Function Block Diagram (FBD)
    • Continuous Function Chart (CFC)
    • Structured Text (ST)
    • Sequential Function Chart (SFC)
  • Programming environment WAGO-I/O-PRO V2.3 (based on CODESYS V2.3)
  • Configuration options
    • WAGO-I/O-CHECK
    • Web-Based Management
    • CODESYS Library
  • Baud rate (communication/fieldbus 1)10/100 Mbit/s
  • Transmission rate 10/100 Mbit/s
  • Transmission medium (communication/fieldbus) Twisted Pair S-UTP; 100 Ω; Cat. 5; 100 m maximum cable length
  • Transmission performance Class D per EN 50173
  • Program memory 8 MB
  • Data memory 8 MB
  • Non-volatile software memory 32kbyte
  • Type of memory card SD card
  • Memory card slot Push-push mechanism; Cover lid (sealable)
  • Number of modules per node (max.) 64
  • Number of modules without a bus extension (max.) 64
  • Input and output process image (fieldbus) max.1020 words/1020 words
  • Indicators LED (LINK/ACT) green: Network connection via ports 1 … 2; LED (MS, NS) red/green: Status of node, network; LED (I/O, USR) red/green/orange: Local data bus status, status
  • programmable by user; LED (A, B) green: System power supply status, field supply
  • Derating
    • Derating (supply voltage):
    • Ambient temperatures under laboratory conditions: (−25 … +30 %);
    • for −40 … +55 °C: 24 V (−25 … +20 %);
    • for +55 … +70 °C: 24 V (−25 … +10 %);
    • Lower limit in all temperature ranges: −27.5 % (including 15 % residual ripple)
  • Supply voltage (system) 24 VDC; via pluggable connector (CAGE CLAMP® connection); Derating must be observed!
  • Input current (typ.) at nominal load (24 V) 500mA
  • Power supply efficiency (typ.) at nominal load (24 V) 90%
  • Current consumption (5 V system supply) 440mA
  • Total current (system supply) 1,700mA
  • Supply voltage (field) 24 VDC; Power supply via pluggable connector (CAGE CLAMP® connection); Transmission via power jumper contacts; Derating must be observed!
  • Current carrying capacity (power jumper contacts) 10A
  • Number of outgoing power jumper contacts 2
  • Rated surge voltage1 kV
  • Connection technology: communication/fieldbusModbus (TCP, UDP): 2 x RJ-45
  • Connection technology: system supply 2 x CAGE CLAMP®
  • Connection technology: field supply 4 x CAGE CLAMP®
  • Connection type 1 System/field supply
  • Solid conductor 0.25 … 2.5 mm² / 24 … 14 AWG
  • Fine-stranded conductor 0.25 … 2.5 mm² / 24 … 14 AWG
  • Strip length 8 … 9 mm / 0.31 … 0.35 inches
  • Connection technology: device configuration1 x Male connector; 4-pole
  • Weight 149.9g
  • Housing material Polycarbonate; polyamide 6.6
  • Conformity marking CE
  • Ambient temperature (operation) -40 … +70 °C
  • Ambient temperature (storage) -40 … +85 °C
  • Protection type IP20
  • Pollution degree 2 per IEC 61131-2
  • Operating altitude without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)
  • Relative humidity (without condensation) 95%
  • Relative humidity (with condensation) Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
  • Mounting position Horizontal left, horizontal up, vertical top and vertical bottom
  • Mounting type DIN-35 rail
  • Vibration resistance per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155; EN 61373
  • Shock resistance per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 50155, EN 61373
  • EMC immunity to interference per EN 61000-6-1, -2; EN 61131-2; marine applications; EN 50121-3-2; EN 50121-4, -5; EN 60255-26; EN 60870-2-1; EN 61850-3; IEC 61000-6-5; IEEE 1613; VDEW: 1994
  • EMC emission of interference per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5
  • Exposure to pollutants per IEC 60068-2-42 and IEC 60068-2-43
  • Fire load 2.487MJ
  • Permissible pollutant concentration H2S at a relative humidity < 75% 10ppm
  • Permissible pollutant concentration SO 2 at a relative humidity < 75% 25ppm

Provided by 
Authorized Distributor

Have questions? Call 800-225-6102

Email sales@atech-inc.com

More Information
Is FM No
Copyright 1995-2026 © Kele Industrial Automation (Lesman | A-Tech Inc | AC Controls | Ponton Industries)