Price
$666.69
Call for Availability
SKU
750-455/040-000
4-channel analog input; 4-20 mA; Single-ended; Extreme Temperature
- Number of analog inputs 4
- Number of Channels 4
- Signal type Current
- Signal type (current) 4 … 20 mADC
- Sensor connection 4 x (2-wire)
- Input voltage (max.) 32 V
- Signal characteristics Single-ended
- Resolution [bit] 12Bit
- Input resistance (max.) 100Ω
- Data width 4 x 16-bit data; 4 x 8-bit control/status (optional)
- Conversion time (typ. ≤) 10ms
- Measurement error, reference temperature 25°C
- Measurement error, deviation max (upper-range value) ≤± 0.1%
- Temperature error max. (upper-range value) ≤± 0.01%/K
- Supply voltage (system) 5 VDC; via data contacts
- Current consumption (5 V system supply) 65mA
- Supply voltage (field) 24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission via spring contact); Derating must be observed
- Dielectric strength 510 VAC / 775 VDC; per EN 60870-2-1
- Rated surge voltage 1 kV
- Indicators LED (A, E, C, G) red: Error AI 1 … AI 4
- Number of incoming power jumper contacts 2
- Number of outgoing power jumper contacts 2
- Current carrying capacity (power jumper contacts) 10A
- Connection technology: inputs / outputs 8 x CAGE CLAMP®
- Connection type 1 Inputs/outputs
- Solid conductor 0.25 … 2.5 mm² / 24 … 14 AWG
- Fine-stranded conductor 0.25 … 2.5 mm² / 24 … 14 AWG
- Strip length 8 … 9 mm / 0.31 … 0.35 inches
- Width 12 mm / 0.472 inches
- Height 100 mm / 3.937 inches
- Depth67.8 mm / 2.669 inches
- Depth from upper-edge of DIN-rail60.6 mm / 2.386 inches
- Mounting type DIN-35 rail
- Color dark gray
- Housing material Polycarbonate; polyamide 6.6
- Fire load 0.958MJ
- Weight 51.3g
- Conformity marking CE
- Ambient temperature (operation) -40 … +70 °C
- Protection type IP20
- Pollution degree 2 per IEC 61131-2
- Operating altitude Without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)
- Mounting position Horizontal left, horizontal up, vertical top and vertical bottom
- Relative humidity (without condensation) 95%
- Relative humidity (with condensation) Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
- Vibration resistance Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155; EN 61373
- Shock resistance Per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 50155, EN 61373
- EMC immunity to interference per EN 61000-6-1, -2; EN 61131-2; marine applications; EN 50121-3-2; EN 50121-4, -5; EN 60255-26; EN 60870-2-1; EN 61850-3; IEC 61000-6-5; IEEE 1613; VDEW: 1994
- EMC emission of interference Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5
- Exposure to pollutants Per IEC 60068-2-42 and IEC 60068-2-43
- Permissible pollutant concentration H2S at a relative humidity < 75% 10ppm
- Permissible pollutant concentration SO 2 at a relative humidity < 75% 25ppm
| Is FM | No |
|---|