WAGO 750-455/040-000 4-Channel Analog Input XTR IO Module [51259088]

Price $666.69
Call for Availability
SKU
750-455/040-000

4-channel analog input; 4-20 mA; Single-ended; Extreme Temperature

  • Number of analog inputs 4
  • Number of Channels 4
  • Signal type Current
  • Signal type (current) 4 … 20 mADC
  • Sensor connection 4 x (2-wire)
  • Input voltage (max.) 32 V
  • Signal characteristics Single-ended
  • Resolution [bit] 12Bit
  • Input resistance (max.) 100Ω
  • Data width 4 x 16-bit data; 4 x 8-bit control/status (optional)
  • Conversion time (typ. ≤) 10ms
  • Measurement error, reference temperature 25°C
  • Measurement error, deviation max (upper-range value) ≤± 0.1%
  • Temperature error max. (upper-range value) ≤± 0.01%/K
  • Supply voltage (system) 5 VDC; via data contacts
  • Current consumption (5 V system supply) 65mA
  • Supply voltage (field) 24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission via spring contact); Derating must be observed
  • Dielectric strength 510 VAC / 775 VDC; per EN 60870-2-1
  • Rated surge voltage 1 kV
  • Indicators LED (A, E, C, G) red: Error AI 1 … AI 4
  • Number of incoming power jumper contacts 2
  • Number of outgoing power jumper contacts 2
  • Current carrying capacity (power jumper contacts) 10A
  • Connection technology: inputs / outputs 8 x CAGE CLAMP®
  • Connection type 1 Inputs/outputs
  • Solid conductor 0.25 … 2.5 mm² / 24 … 14 AWG
  • Fine-stranded conductor 0.25 … 2.5 mm² / 24 … 14 AWG
  • Strip length 8 … 9 mm / 0.31 … 0.35 inches
  • Width 12 mm / 0.472 inches
  • Height 100 mm / 3.937 inches
  • Depth67.8 mm / 2.669 inches
  • Depth from upper-edge of DIN-rail60.6 mm / 2.386 inches
  • Mounting type DIN-35 rail
  • Color dark gray
  • Housing material Polycarbonate; polyamide 6.6
  • Fire load 0.958MJ
  • Weight 51.3g
  • Conformity marking CE
  • Ambient temperature (operation) -40 … +70 °C
  • Protection type IP20
  • Pollution degree 2 per IEC 61131-2
  • Operating altitude Without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)
  • Mounting position Horizontal left, horizontal up, vertical top and vertical bottom
  • Relative humidity (without condensation) 95%
  • Relative humidity (with condensation) Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
  • Vibration resistance Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155; EN 61373
  • Shock resistance Per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 50155, EN 61373
  • EMC immunity to interference per EN 61000-6-1, -2; EN 61131-2; marine applications; EN 50121-3-2; EN 50121-4, -5; EN 60255-26; EN 60870-2-1; EN 61850-3; IEC 61000-6-5; IEEE 1613; VDEW: 1994
  • EMC emission of interference Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5
  • Exposure to pollutants Per IEC 60068-2-42 and IEC 60068-2-43
  • Permissible pollutant concentration H2S at a relative humidity < 75% 10ppm
  • Permissible pollutant concentration SO 2 at a relative humidity < 75% 25ppm