Fireye Flame Monitor Series ED510 Display Module

The ED510 display module is one of the components in Fireye's Flame-Monitor Series Burner Control System, which provides the proper burner sequencing, ignition and flame monitoring protection on automatically ignited oil, gas and combustion fuel burners. The ED510 mounts directly onto the front face of programmers either before or after the programmer is installed in the chassis.

Current burner status, first out annunciation in the event of a lockout condition, historical burner information, detailed lockout information of the last six lockout conditions, and diagnostic messages are all displayed on the ED510 in order to provide the operator with the most significant information available.

Key Specifications

  • LCD backlit display with 2 lines of 16 characters each
  • Keypad provides historical data from the burner, plus the last six lockout conditions
  • Includes an RJ style connector compatible with the EP160 programmer module
  • Remote display capability using DIN-sized opening and remote mounting kit
  • NEMA 4 weather-proof housing

Specifications, Manuals, and Supporting Literature

Click the file icon to view the file online, or right-click on the file icon and select "Save Target As..." to download the file to your computer for later viewing.
Tip: If you want to print a large file, download it to your PC first.

Model Selection Guide

Use this table to find the right model for your application.  Don't see the option you need? Call a Lesman sales specialist at 800-953-7626

Description Catalog Number
Control Chassis 120 VAC Burner Control Chassis with Mounting Screws and Dust Cover  E110
Program Module 30-Second Purge, 10/15 Second TFI, 4 Second FFRT, Non-Recycle Modulation  EP160
Display Module Two-Line x 16-Character LCD Display with Keypad  ED510
Ultraviolet Flame
Scanner/Amplifier
Non Self-Checking UV Scanner, 3Ft Flexible Cable, 1/2" NPT Connection 
Non Self-Checking Scanner, 6Ft Flexible Cable, 1/2" NPT Connection
Standard Ultraviolet Flame Amplifier Module
UV1A3
UV1A6
EUV1
Self-Checking UV Scanner, 120 VAC Shutter, 1" NPT Thread 
Self-Check Ultraviolet Flame Amplifier Module
45UV5-1009
EUVS4
Infrared Flame
Scanner/Amplifier
Infrared Scanner 8Ft Shielded Cable with 90° Head
Autocheck Infrared Flame Amplifier Module
48PT2-9003
E1R1
Flame Rod/
Amplifier
12" Flame Rod for Gas Flames, 1/2" NPT Connection
Flame Rectification Amplifier Module
69ND1-1000K4
ERT1
Wiring Base Surface-Mount Wiring Base
Panel-Mount Wiring Base
60-1386-2
60-1466-2

A complete Flame Monitor system includes the E110 flame safety control chassis plus a EP160 program module, ED510 display module, discrete flame scanner (UV1, 48PT2, 45UV5 or 69ND1 flame rod) with compatible amplifier module, and wiring base.

Videos

Subscribe to the Lesman Instrument Company YouTube channel.Lesman Instrument Company on YouTube

Video is a great way to learn about instruments and technology, and it's available whenever you need it. Watch step-by-step instructions on how to configure a transmitter, tune a controller, or troubleshoot a safety valve. We'll post videos we create, and those our manufacturer partners share with us, so you don't have to look in multiple places to find the video training you need.

Subscribe to Lesman's YouTube channel, and you'll get email notifications as soon as we add new training videos and webinars.